Parallel-redundant capable
Power the connected equipment with multiple uninterruptible power supplies to increase system redundancy
-
Parallel-capacity capable
Increases total power capacity by using multiple uninterruptible power supplies simultaneously.
-
Multiple cable-entry points
Provides flexibility of UPS placement in the room and easy access to install cabling to the terminal blocks.
-
Scalable runtime
Allows additional run time to be quickly added as needed.
-
Front-access servicing
Simplifies installation and UPS maintenance while minimizing space requirements.
-
Scalable power capacity
Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
-
Compatible with Schneider Electric's lithium ion battery solution
Reduces system footprint and weight, cooling and maintenance requirements, and total cost of ownership; offers double the life of VRLA batteries; and improves backup storage predictablity and manageability.
-
Temperature-compensated battery charging
Prolongs battery life by regulating the charge voltage according to battery temperature.
-
Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
-
Intelligent battery management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
-
Manageable external batteries
Reduces preventative maintenance service needs by monitoring the health and status of the external batteries and their expected runtime.
-
Fully-rated power kVA equals kW
Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
-
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
-
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
-
Configurable for N+1 internal redundancy
Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
-
Network manageable
Provides remote power management of the UPS over the network.
-
Audible alarms
Provides notification of changing utility power and UPS power conditions
-
Power Modules connected in parallel
Enhances availability by allowing immediate, seamless recovery from isolated module failures.
-
Modular design
Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
-
Battery failure notification
Provides early-warning fault analysis on batteries enabling timely preventive maintenance
-
Scalable power capacity
Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
-
Battery modules connected in parallel
Delivers higher availability through redundant batteries.
-
LCD display
Provides schematic overview of critical data for guided operation and troubleshooting on color LCD touch-screen.
-
Modular design
Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
-
Input power factor correction
Eliminates the need for an external phase-compensation unit and minimizes installation costs by enabling the use of smaller generators and cabling.
-
Fully-rated power kVA equals kW
Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
-
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
-
Power Modules connected in parallel
Enhances availability by allowing immediate, seamless recovery from isolated module failures.
-
Configurable for N+1 internal redundancy
Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
Output
-
Output power capacity
1.6 MWatts / 1.6 MVA
-
Max Configurable Power (Watts)
1.6 MWatts / 1.6 MVA
-
Nominal Output Voltage
400V 3PH
-
Output Voltage Note
Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
-
Output Voltage Distortion
Less than 5% at full load
-
Output Frequency (sync to mains)
50 Hz - programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8%
-
Output Frequency (not synced)
50Hz +/- 0.1% for 50Hz nominal
-
Other Output Voltages
380, 415
-
Load Crest Factor
Unlimited
-
Topology
Delta Conversion On-Line
-
Waveform type
Sine wave
-
Maximum Output Current
2940
-
Output Connections
(1) Hard Wire 5-wire (3PH + N + G) (Battery Backup)
(1) Hard Wire 4-wire (3PH + N) (Battery Backup)
(1) Hard Wire 4-wire (3PH + G) (Battery Backup)
(1) Hard Wire 4-wire (3PH - PEN) (Battery Backup)
-
Bypass
External Static Bypass
Input
-
Nominal Input Voltage
400V 3PH
-
Input frequency
50 Hz - programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8%
-
Input Connections
Hard Wire 4-wire (3PH + G), Hard Wire 4-wire (3PH + PEN), Hard Wire 5-wire (3PH + N + G)
-
Input voltage range for main operations
323 - 437 (380V), 340 - 460 (400V), 353 - 477 (415V)V
-
Input voltage adjustable range for mains operation
323 - 437 (380V), 340 - 460 (400V), 357 - 477 (415V)V
-
Number of Power Cords
1
-
Other Input Voltages
380, 415
-
Input Power Factor at Full Load
0.99
Batteries & Runtime
-
Battery type
No internal battery - uses external battery system
-
Extendable Run Time
1
-
Extended Run Options
Symmetra-MW-1600kW-Frame-400V
-
Efficiency
Communications & Management
Physical
-
Maximum Height
2032mm , 203.2cm
-
Maximum Width
5486mm , 548.6cm
-
Maximum Depth
1067mm , 106.7cm
-
Net Weight
6376.36kg
-
Shipping weight
6576.36kg
-
Shipping Height
2235mm , 223.5cm
-
Shipping Width
6240mm , 624.0cm
-
Shipping Depth
1280mm , 128.0cm
-
Color
Light grey (NCS 2703-G84Y)
-
Units per Pallet
1.0
Environmental
-
Operating Environment
0 - 40 °C
-
Operating Relative Humidity
0 - 95 %
-
Operating Elevation
0-999.9meters
-
Storage Temperature
-50 - 40 °C
-
Storage Relative Humidity
0 - 95 %
-
Storage Elevation
0-15000meters
-
Audible noise at 1 meter from surface of unit
75.0dBA
-
Online thermal dissipation
168960.0BTU/hr
-
Protection Class
IP 20
Conformance
-
Approvals
CE, EN 50091-1, EN 50091-2, EN 50091-3, EN 60950, EN/IEC 62040-3, FCC Part 15 Class A, IEC 60950, ISO 14001, ISO 9001, VFI-SS-111
-
Standard warranty
1 year repair or replace