Galaxy VX 1000kVA Scalable to 1250kVA 400V, Start up 5x8
Highly efficient, scalable, 3-phase power protection with flexible operating modes for large facilities, data centers, and business critical applications.
Includes: Installation guide , Network Management Card , Start-Up Service
Galaxy VXFeatures & Benefits
Total Cost of Ownership
-
Robust operation
No power derating in kW up to 40 degrees C or 104 degrees F.
-
Wide input voltage range
Designed for harsh electrical environments to save battery life.
-
ECOnversion mode
Operating mode that ensures ultra high efficiency while charging the batteries, conditioning the load power factor and ensuring a Class 1 output voltage regulation.
-
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
-
ECO Mode
Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection
Availability
-
Parallel-redundant capable
Power the connected equipment with multiple uninterruptible power supplies to increase system redundancy
-
Energy storage flexibility
Conventional flooded and modular battery offer along with different charging modes allows tailoring to specific back-up requirements.
-
Internal backfeed protection
Increases system defense from power anomalies.
-
Compatible with Schneider Electric's lithium ion battery solution
Reduces system footprint and weight, cooling and maintenance requirements, and total cost of ownership; offers double the life of VRLA batteries; and improves backup storage predictablity and manageability.
-
Parallel-capacity capable
Increases total power capacity by using multiple uninterruptible power supplies simultaneously.
Serviceability
-
5x8 Start-up service included
Required for full coverage of factory warranty
-
Front-access servicing
Simplifies installation and UPS maintenance while minimizing space requirements.
-
StruxureWare Data Center Expert compatible
Enables centralized management via StruxureWare Data Center Expert.
-
Multiple levels of service
With the option of packages or individual service components, our services are structured to allow you to pick and choose what you would like APC to do for you.
Output
-
Output power capacity
1.0 MWatts / 1.0 MVA
-
Max Configurable Power (Watts)
1.25 MWatts / 1.25 MVA
-
Nominal Output Voltage
400V 3PH
-
Output Frequency (sync to mains)
50 Hz
-
Output Frequency (not synced)
50Hz +/- 0.1% for 50Hz nominal
-
Other Output Voltages
380, 415
-
Load Crest Factor
3 with THC <5%
-
Topology
Double Conversion Online
-
Waveform type
Sine wave
-
Overload Operation
150% for 1 minute 125% for 10 minutes
-
Output Voltage THD
< 2% linear load and <3% non-linear load
Input
-
Nominal Input Voltage
400V 3PH
-
Input frequency
40 - 70 Hz
-
Input Connections
Hard Wire 4-wire (3PH + G)
-
Input Total Harmonic Distortion
Less than 3% for full load
-
Other Input Voltages
380, 415
-
Maximum Short Circuit Withstand (Icw)
100.0kAmps
-
Maximum Input Current
1702.0A
-
Input Power Factor at Full Load
1.0
Batteries & Runtime
Communications & Management
Physical
-
Maximum Height
1970mm , 197.0cm
-
Maximum Width
4400mm , 440.0cm
-
Maximum Depth
900mm , 90.0cm
-
Net Weight
2910.0kg
-
Shipping weight
3737.0kg
-
Shipping Height
2150mm , 215.0cm
-
Shipping Width
5160mm , 516.0cm
-
Shipping Depth
1060mm , 106.0cm
-
Color
White
Environmental
-
Operating Environment
0 - 40 °C
-
Operating Relative Humidity
0 - 95% non-condensing %
-
Operating Elevation
0-999.9meters
-
Storage Temperature
-15 - 40 °C
-
Storage Relative Humidity
0 - 95% non-condensing %
-
Storage Elevation
0-15000meters
-
Audible noise at 1 meter from surface of unit
68.0dBA
-
Online thermal dissipation
174332.0BTU/hr
-
Protection Class
IP 20
Conformance
-
Approvals
C-tick, CE, EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, IBC 2012, ISTA 2B
-
Standard warranty
1 year on-site repair or replace with factory authorized Start-Up