InRow RP DX Air Cooled 380-415V 50 Hz
Includes: Installation Guide , Operations and Maintenance Manual
ACRP102Features
InRow RP DX Air Cooled 380-415V 50 Hz
-
Containment system compatible
The unit can be combined with a Rack or Hot Aisle Containment System to eliminate hot air mixing and maximize cooling efficiency
-
Electric Reheat
Prevents overcooling during dehumidification.
-
Humidifier
Humidity is managed through a self-contained steam canister humidifier for maximum efficiency and ease of maintenance. The pure steam canister maintains consistent capacity output, and requires very little or no scheduled maintenance.
InRow Direct ExpansionFeatures & Benefits
Agility
-
Scaleable densities
Allows for higher densities to be achieved by integrating containment with room, row and rack cooling system architectures.
-
Modular design
Modular design provides scalable solutions to add cooling as demand increases.
Serviceability
Total Cost of Ownership
-
Variable speed fans
Variable speed fans reduce energy consumption during off-peak cooling periods.
-
In-Row architecture
Captures hot exhaust air directly from the IT equipment, thereby increasing the unit's sensible cooling capacity over traditional cooling architectures.
Manageability
-
Real-Time capacity monitoring
Real-time display of current and available cooling.
-
Microprocessor controller
Utilizes intelligent, active response control, and real-time monitoring. The system is controlled by a microprocessor providing high level control functionality and human interface via a four line, eighty character, alphanumeric display
-
Building management system integration
Send alarms and data points allowing you to manage critical building infrastructure from a single system.
Availability
-
Rack inlet temperature control
Reduces the risk of hot spots at the rack level
-
Active response controls
Monitors and actively adjusts cooling capacity to ensure proper server inlet temperatures. Through the microprocessor controller, visibility into the operation and health of the unit is provided.
-
Predictable cooling
Placing the unit in the row of racks moves the source of cooling closer to the heat load. This eliminates air mixing and provides a predictable cooling architecture.
Input
-
Nominal Input Voltage
400V 3PH
-
Input Connections
Hard Wire 4-wire (3PH + G)
-
Input Power
20000.0Watts
Communications & Management
-
Control panel
Multi-function LCD status and control console
-
Audible Alarm
Audible and visible alarms prioritized by severity
Physical
-
Maximum Height
1991mm , 199.1cm
-
Maximum Width
600mm , 60.0cm
-
Maximum Depth
1070mm , 107.0cm
-
Rack Height
42U
-
Net Weight
378.64kg
-
Shipping weight
489.09kg
-
Shipping Height
2166mm , 216.6cm
-
Shipping Width
850mm , 85.0cm
-
Shipping Depth
1137mm , 113.7cm
-
Color
Black
-
Units per Pallet
1.0
Conformance
-
Approvals
C-tick, CE, GOST
-
Standard warranty
1 year (parts only), 1 year on-site repair or replace with factory authorized Start-Up
Sustainable Offer Status
General
-
Air Discharge Patterns
Horizontal
-
Air Flow
2170.96lps
-
Compressor Type
Reciprocating
-
Condensate Pump Capacity
0.008lps
-
Humidification Value
6.6pounds/hour
-
Intake Air
Rear Return