Maintenance Bypass Panels
APC Service Bypass Panel- 230V; 100A; MBB; Hardwire input; (3) 30A Hardwire Output
Extremely reliable service bypass panels designed for APC InfraStruXure® Type A, Smart-UPS, and Symmetra UPS products.
APC Maintenance Bypass Panels, Input: 230V, Input Connections: Hard Wire 3 wire (1PH+N+G), Hard Wire 4-wire (3PH + G), Output: 230V, Output Connections: Hard Wire 3-wire (H N + G)
Includes: Installation guide, Rack Mounting brackets, User Manual
Wrap Around System Bypass
(3) Breaker maintenance bypass panel to isolate the UPS from the critical load
Nominal Output Voltage
230V
Maximum Total Current Draw per Phase
100A
Output Connections
(3) Hard Wire 3-wire (H N + G)
|
|
Nominal Input Voltage
230V
Input Connections
Hard Wire 3 wire (1PH+N+G)
|
|
Hard Wire 4-wire (3PH + G)
|
|
Maximum Line Current per phase
100A
Maximum Input Current per phase
100A
Load Power Factor Range
0 to 1
Net Weight
48.00 lbs. (21.82 kg)
Maximum Height
7.00 inches (178 mm)
Maximum Width
17.00 inches (432 mm)
Maximum Depth
26.50 inches (673 mm)
Shipping Weight
70.00 lbs. (31.82 kg)
Shipping Height
12.00 inches (305 mm)
Shipping Width
24.00 inches (610 mm)
Shipping Depth
39.00 inches (991 mm)
Operating Environment
-4 - 113 °F (-20 - 45 °C)
Operating Relative Humidity
0 - 95%
Operating Elevation
0-15000 feet (0-4500 meters)
Storage Temperature
-40 - 149 °F (-40 - 65 °C)
Storage Relative Humidity
0 - 95%
Storage Elevation
0-50000 feet (0-15000 meters)
Regulatory Approvals
CSA, EN 60950, GOST, IEC 60950, IEC 60950, UL 1778
Standard Warranty
2 years (parts only)