Scalable power capacity
Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
-
Modular design
Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
-
Battery modules connected in parallel
Delivers higher availability through redundant batteries.
-
Power Modules connected in parallel
Enhances availability by allowing immediate, seamless recovery from isolated module failures.
-
Network manageable
Provides remote power management of the UPS over the network.
-
Fully-rated power kVA equals kW
Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
-
User-replaceable power modules
Enables simple upgrades and replacements of the Power Modules.
-
Configurable for N+1 internal redundancy
Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
-
User-replaceable batteries
Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
-
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
Output
-
Output power capacity
160.0 KWatts / 160.0 kVA
-
Max Configurable Power (Watts)
160.0 KWatts / 160.0 kVA
-
Nominal Output Voltage
230V , 400V 3PH
-
Neutral Output Current
400A
-
Output Voltage Note
Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
-
Output Voltage Distortion
Less than 2%
-
Output Frequency (sync to mains)
50/60 Hz +/- 3 Hz user adjustable +/- 0.1
-
Output Frequency (not synced)
50Hz +/- 0.1% for 50Hz nominal
-
Topology
Double Conversion Online
-
Waveform type
Sine wave
-
Overload Operation
10 minutes @ 125% and 60 seconds @ 150%
-
Output Voltage THD
< 2% for 0 to 100% linear load and < 6% for full non linear load
-
Output Voltage Tolerance
+/-1% static and +/- 5% at 100% load step
-
Bypass
Built-in Static Bypass
Input
-
Nominal Input Voltage
400V 3PH
-
Input frequency
40 - 70 Hz
-
Input Connections
Hard Wire 5-wire (3PH + N + G)
-
Input voltage range for main operations
340 - 477V
-
Input Total Harmonic Distortion
Less than 5% for full load
-
Maximum Short Circuit Withstand (Icw)
30.0kAmps
-
Maximum Input Current
295.0A
-
Input Power Factor at Full Load
0.99
Batteries & Runtime
-
Battery type
VRLA
-
Included Battery Modules
15
-
Typical recharge time
3.5hour(s)
-
Nominal Battery Voltage
+/-192 V (split battery referenced to neutral)
-
End of Discharge Maximum Battery Current
550.0A
-
Battery Slots Empty
3
-
RBC Quantity
4
-
DC Overcurrent Protection
945A
-
Extendable Run Time
1
-
End of Discharge Battery Voltage
+/-154 V
-
Efficiency in Battery Operation
94.0 %
-
Maximum Available Short Circuit Current
10kAmps
-
Overload Operation
10 minutes @ 125% and 60 seconds @ 150%
-
Runtime
-
Efficiency
Communications & Management
Physical
-
Maximum Height
1991mm , 199.1CM
-
Maximum Width
1800mm , 180.0CM
-
Maximum Depth
1070mm , 107.0CM
-
Rack Height
42U
-
Net Weight
2878.0KG
-
Shipping weight
3116.0KG
-
Shipping Height
2140mm , 214.0CM
-
Shipping Width
2235mm , 223.5CM
-
Shipping Depth
1210mm , 121.0CM
-
Color
Black
Environmental
-
Operating Temperature
0 - 40 °C
-
Operating Relative Humidity
0 - 95 %
-
Operating Elevation
0-999.9meters
-
Storage Temperature
-15 - 40 °C
-
Storage Relative Humidity
0 - 95 %
-
Storage Elevation
0-15000meters
-
Audible noise at 1 meter from surface of unit
63.0dBA
-
Online thermal dissipation
28741.0BTU/hr
-
Protection Class
NEMA 1, IP 20
Conformance
-
Approvals
EN 50091-1, EN/IEC 62040-1-1, EN/IEC 62040-2, EN/IEC 62040-3, Eurobat General Purpose, ISO 14001, ISO 9001, VFI-SS-111
-
Standard warranty
1 year on-site repair or replace with factory authorized Start-Up
General
-
Bypass Connection
5 wire (3PH + N + G)
-
Bypass Protection Device
250.0
-
Max Bypass Input Current
250.0A